LINE is the cable from the panel; LOAD feeds the outlets after this one. Black (hot) goes to brass, white (neutral) to silver, bare to green. Put LINE on the LINE terminals: a modern GFCI locks out if LINE and LOAD are swapped. Use the LOAD terminals only to protect outlets downstream; spliced through with the line instead, they still work but aren't protected. On a real job: breaker off, then prove it dead with a tester before you touch a wire.