Convert temperature and relative humidity to grains per pound (GPP) — the specific humidity restorers track, because RH alone hides how much water the air is actually holding.
GPP chart by temperature and relative humidity
Grains per pound at sea level. Values at 90 GPP and above are highlighted; that is wetter than comfortable indoor air.
| Temp °F | 30% RH | 40% RH | 50% RH | 60% RH | 70% RH | 80% RH | 90% RH |
|---|---|---|---|---|---|---|---|
| 60°F | 23 | 31 | 38 | 46 | 54 | 62 | 69 |
| 65°F | 27 | 37 | 46 | 55 | 64 | 74 | 83 |
| 70°F | 33 | 43 | 54 | 66 | 77 | 88 | 99 |
| 75°F | 39 | 52 | 65 | 78 | 91 | 104 | 118 |
| 80°F | 46 | 61 | 76 | 92 | 108 | 124 | 140 |
| 85°F | 54 | 72 | 90 | 109 | 127 | 146 | 165 |
| 90°F | 63 | 84 | 106 | 128 | 150 | 172 | 195 |
What is GPP (grains per pound)?
Grains per pound is the weight of water vapor carried by one pound of dry air. A grain is a tiny unit of weight — 7,000 grains make one pound — so 70 GPP means every pound of dry air in the room is carrying 70/7,000 of a pound of water as vapor. In psychrometric terms GPP is the humidity ratio; the restoration industry often calls it specific humidity.
The reason restorers care: relative humidity is relative to temperature. Warm the same air and its RH falls, even though not one drop of water has left the room. GPP does not move when the temperature moves. It changes only when water is actually added to the air (evaporating from wet materials) or removed from it (by a dehumidifier or by air exchange). That makes it the honest number for tracking whether a structure is drying.
Example: air at 70°F and 60% RH holds about 65.5 GPP. Heat that room to 80°F without removing any moisture and the RH drops to roughly 43% — it looks much drier on the meter — but it is still 65.5 GPP. Nothing has been dried yet.
The GPP formula, step by step
This calculator uses the standard psychrometric relationships. Here is the full calculation for 75°F at 55% RH, so you can check it by hand:
- Convert to Celsius. T = (75 − 32) × 5/9 = 23.89°C.
- Saturation vapor pressure (Magnus–Tetens): Psat = 0.61078 × e17.27·T / (T + 237.3) = 2.964 kPa. This is the most vapor the air could hold at that temperature.
- Actual vapor pressure: Pv = RH × Psat = 0.55 × 2.964 = 1.630 kPa.
- Humidity ratio: W = 0.622 × Pv ÷ (P − Pv), with sea-level pressure P = 101.325 kPa (29.92 inHg). W = 0.622 × 1.630 ÷ 99.695 = 0.01017 lb of water per lb of dry air.
- Grains per pound: GPP = W × 7,000 = 71.2 GPP.
Dew point comes from the same vapor pressure: solve the Magnus equation backwards for the temperature at which 1.630 kPa would be saturated. For this example that is 14.3°C, or 57.7°F. The Magnus approximation tracks the ASHRAE psychrometric tables closely (within about one percent) across normal drying temperatures — far tighter than the accuracy of a field thermo-hygrometer.
Altitude matters. The formula divides by atmospheric pressure, and pressure falls as you climb. The same 75°F / 55% RH reading is about 71 GPP at sea level but about 86 GPP at 5,000 feet. This calculator assumes sea level; if you work at elevation, use a meter or app that lets you set the station pressure, and stay consistent across the job.
Worked example: is the job drying?
Day 1, the affected room reads 78°F and 65% RH: 93.4 GPP, dew point 65.3°F. Day 3, it reads 78°F and 40% RH: 57.0 GPP, dew point 51.7°F. The temperature never changed, but the air now holds 36 fewer grains of water per pound.
That drop is half of the evidence. The other half is the materials: moisture readings in the wet drywall, subfloor, and framing should be trending down toward the drying goal at the same time. Falling GPP with flat material readings usually means the air is being dried but evaporation from the materials is not keeping up — a sign to look at airflow across the wet surfaces, containment, or heat.
How restorers use GPP and grain depression
On a water loss, GPP is logged at a few fixed points every visit so the readings can be compared day over day:
- Affected area — the drying chamber itself. This number should fall as the job progresses.
- Unaffected area — a dry room in the same building. It is the reference for what “normal” air looks like in that structure.
- Outdoors — tells you whether opening the building would help or hurt. If outdoor air is wetter in GPP than the chamber, ventilating adds water.
- Dehumidifier exhaust — the air leaving each unit.
The difference between the air entering a dehumidifier and the air leaving it is the grain depression. Inlet 78°F / 65% RH (93.4 GPP) and outlet 90°F / 22% RH (46.0 GPP) is a 47.4 GPP depression: every pound of air through the coil gives up 47 grains of water. On a wet job, healthy LGR units commonly show 20–40 GPP of depression or more, and the number naturally shrinks as the room dries. Check yours with the grain depression calculator.
Grain depression is a useful diagnostic, but it is not the scorecard. The 2021 IICRC S500 (5th edition) frames drying performance around controlling the environment and confirming that material moisture is falling over time — a big depression in a small, sealed room that is already nearly dry proves little. Log GPP, then confirm with the materials.
Typical GPP targets — and why there is no single number
There is no universal “correct” GPP for a drying chamber; the target depends on the materials, the class of water, the outdoor conditions, and the equipment. What experienced drying techs look for is the relationship between the numbers:
- The affected area’s GPP falls each day and ends at or below the unaffected area.
- Dehumidifier exhaust stays well below the chamber GPP (a positive grain depression).
- The chamber’s dew point stays below the temperature of its coldest surface — windows, slab, exterior walls — so moisture is not condensing and re-wetting materials. The drying goal calculator turns a surface temperature into a maximum GPP.
For comparison, comfortable indoor air is often around 50–60 GPP. Under the 5th edition of S500, the drying goal for a material is set by the restorer using several inputs; a dry-standard reading from similar unaffected material is one of them, not the whole definition. Verify the details against the current edition of the standard.
Common GPP mistakes on the job
- Logging RH instead of GPP. RH swings with every degree of temperature, so day-over-day RH comparisons can show progress that is not there — or hide progress that is.
- Mixing meters. Readings from different instruments drift apart. Use the same meter for a job, or cross-check meters against each other, so the trend is real.
- Taking inlet and outlet readings at different times. Grain depression needs inlet and exhaust measured together, in the airstream, with the same meter.
- Skipping the reference readings. Without unaffected and outdoor GPP there is nothing to compare the chamber against.
- Ignoring altitude. A sea-level calculator under-reads GPP at elevation. Be consistent rather than mixing settings mid-job.
- Treating GPP as the finish line. Dry air is the means; dry materials are the result. The job is done when the materials meet the drying goal, documented with readings.
Logging GPP every day, without the clipboard
Every reading above belongs in the drying log — chamber, unaffected, outdoor, and dehu exhaust, every visit — alongside the material moisture readings. That record is what supports the mitigation invoice when a carrier reviews it. RestoredOS water mitigation software computes GPP and dew point from each atmospheric reading automatically and keeps the daily log on the job file, so the numbers on this page land in the documentation instead of on a notepad.
Frequently asked
What is grains per pound?
Grains per pound (GPP) is the weight of water vapor in the air per pound of dry air — 7,000 grains equal one pound of water. It is a direct measure of how much moisture the air holds, and unlike relative humidity it does not change when the air is heated or cooled.
GPP vs relative humidity — what is the difference?
Relative humidity is a percentage of how much water the air could hold at that temperature, so it changes as the air warms or cools. GPP is an absolute amount that does not change with temperature, which is why restoration techs track it for drying decisions.
How do you calculate grains per pound?
Find the saturation vapor pressure at the air temperature, multiply by the relative humidity to get the vapor pressure, convert it to a humidity ratio (0.622 × Pv ÷ (P − Pv)), and multiply by 7,000. For example, 75°F at 55% RH is about 71 GPP at sea level.
What is a normal indoor GPP?
Comfortable indoor air is often around 50–60 GPP. On an active water loss the affected rooms run much higher, and the aim is to bring them down — at or below the unaffected areas — while keeping the dew point below the coldest surface.
What GPP should the dehumidifier exhaust be?
Lower than the room. The difference between the air going in and the air coming out is the grain depression; a healthy LGR unit commonly shows 20–40 GPP or more when the room is wet. Check it with the grain depression calculator.
Is GPP the same as specific humidity?
Close, but not exactly. GPP is the humidity ratio — water per pound of dry air. Strict specific humidity is water per pound of moist air. At indoor conditions the two differ by about one percent, which is why the restoration industry uses the terms interchangeably.
Does altitude change grains per pound?
Yes. Lower air pressure at elevation means the same temperature and RH carry more grains per pound: 75°F at 55% RH is about 71 GPP at sea level and about 86 GPP at 5,000 feet. This calculator assumes sea-level pressure.
How do I convert GPP to dew point?
Both come from the same vapor pressure. Higher GPP means a higher dew point: about 57 GPP is a 52°F dew point, 93 GPP is about 65°F. This calculator shows both at once.
Related tools